Italy South Daily Load Shape and Duck Curve by Hour, 8 October to 4 November 2026
In the 28 complete local days from 8 October to 4 November 2026, electricity demand in Italy South averaged 2,239 MW and typically peaked at 19:00 local time (2,704 MW) and bottomed out at 03:00 (1,800 MW). With solar and wind taken off, the remaining load fell to -873 MW at 11:00 and then rose 1,489 MW between 15:00 to 18:00. Hours are local clock time (Europe/Rome).
Key Facts
- Over 28 complete local days from 8 October to 4 November 2026, average demand in Italy South was 2,239 MW. The hour of the day with the highest average demand was 19:00 local time (2,704 MW) and the lowest was 03:00 (1,800 MW).
- The largest three hour rise in average demand was 413 MW, between 15:00 to 18:00 local time.
- The single highest hour of demand in the 30 day window was 3,186 MW, in the hour starting 28 Oct 2026, 18:00 CET (UTC+01:00).
- Solar output averaged 1,765 MW at its 11:00 peak, 79% of average demand.
- Demand minus solar and wind (net load) averaged 273 MW, fell to -873 MW at 11:00 and rose 1,489 MW over the three hours from 15:00 to 18:00, 67% of average demand.
Average Day by Local Hour
28 days to 2026-11-04, Europe/Rome time| Local hour (Europe/Rome) | Demand | Net generation |
|---|---|---|
| 00:00 | 2,044 MW | 3,320 MW |
| 01:00 | 1,859 MW | 3,004 MW |
| 02:00 | 1,806 MW | 2,905 MW |
| 03:00 | 1,800 MW | 2,925 MW |
| 04:00 | 1,808 MW | 2,953 MW |
| 05:00 | 1,859 MW | 2,977 MW |
| 06:00 | 2,050 MW | 3,175 MW |
| 07:00 | 2,240 MW | 3,413 MW |
| 08:00 | 2,331 MW | 3,726 MW |
| 09:00 | 2,320 MW | 3,882 MW |
| 10:00 | 2,312 MW | 3,968 MW |
| 11:00 | 2,279 MW | 3,955 MW |
| 12:00 | 2,336 MW | 3,935 MW |
| 13:00 | 2,267 MW | 3,887 MW |
| 14:00 | 2,200 MW | 3,772 MW |
| 15:00 | 2,239 MW | 3,744 MW |
| 16:00 | 2,329 MW | 3,776 MW |
| 17:00 | 2,525 MW | 3,909 MW |
| 18:00 | 2,652 MW | 3,928 MW |
| 19:00 | 2,704 MW | 3,907 MW |
| 20:00 | 2,673 MW | 3,823 MW |
| 21:00 | 2,525 MW | 3,747 MW |
| 22:00 | 2,370 MW | 3,723 MW |
| 23:00 | 2,210 MW | 3,606 MW |
| Local hour (Europe/Rome) | Demand | Net load (demand minus solar and wind) |
|---|---|---|
| 00:00 | 2,044 MW | 630 MW |
| 01:00 | 1,859 MW | 408 MW |
| 02:00 | 1,806 MW | 368 MW |
| 03:00 | 1,800 MW | 371 MW |
| 04:00 | 1,808 MW | 328 MW |
| 05:00 | 1,859 MW | 340 MW |
| 06:00 | 2,050 MW | 456 MW |
| 07:00 | 2,240 MW | 459 MW |
| 08:00 | 2,331 MW | 63 MW |
| 09:00 | 2,320 MW | -412 MW |
| 10:00 | 2,312 MW | -711 MW |
| 11:00 | 2,279 MW | -873 MW |
| 12:00 | 2,336 MW | -803 MW |
| 13:00 | 2,267 MW | -805 MW |
| 14:00 | 2,200 MW | -676 MW |
| 15:00 | 2,239 MW | -339 MW |
| 16:00 | 2,329 MW | 186 MW |
| 17:00 | 2,525 MW | 805 MW |
| 18:00 | 2,652 MW | 1,150 MW |
| 19:00 | 2,704 MW | 1,264 MW |
| 20:00 | 2,673 MW | 1,290 MW |
| 21:00 | 2,525 MW | 1,177 MW |
| 22:00 | 2,370 MW | 1,018 MW |
| 23:00 | 2,210 MW | 857 MW |
| Local hour (Europe/Rome) | Solar | Wind |
|---|---|---|
| 00:00 | 0 MW | 1,415 MW |
| 01:00 | 0 MW | 1,451 MW |
| 02:00 | 0 MW | 1,438 MW |
| 03:00 | 0 MW | 1,429 MW |
| 04:00 | 0 MW | 1,481 MW |
| 05:00 | 0 MW | 1,520 MW |
| 06:00 | 12 MW | 1,582 MW |
| 07:00 | 211 MW | 1,571 MW |
| 08:00 | 744 MW | 1,524 MW |
| 09:00 | 1,288 MW | 1,444 MW |
| 10:00 | 1,613 MW | 1,410 MW |
| 11:00 | 1,765 MW | 1,388 MW |
| 12:00 | 1,749 MW | 1,390 MW |
| 13:00 | 1,623 MW | 1,449 MW |
| 14:00 | 1,377 MW | 1,498 MW |
| 15:00 | 955 MW | 1,623 MW |
| 16:00 | 459 MW | 1,684 MW |
| 17:00 | 109 MW | 1,611 MW |
| 18:00 | 2 MW | 1,500 MW |
| 19:00 | 1 MW | 1,440 MW |
| 20:00 | 0 MW | 1,383 MW |
| 21:00 | 0 MW | 1,348 MW |
| 22:00 | 0 MW | 1,353 MW |
| 23:00 | 0 MW | 1,352 MW |
| Local hour | Demand | Net generation | Solar | Wind | Net load |
|---|---|---|---|---|---|
| 00:00 | 2,044 MW | 3,320 MW | 0 MW | 1,415 MW | 630 MW |
| 01:00 | 1,859 MW | 3,004 MW | 0 MW | 1,451 MW | 408 MW |
| 02:00 | 1,806 MW | 2,905 MW | 0 MW | 1,438 MW | 368 MW |
| 03:00 | 1,800 MW | 2,925 MW | 0 MW | 1,429 MW | 371 MW |
| 04:00 | 1,808 MW | 2,953 MW | 0 MW | 1,481 MW | 328 MW |
| 05:00 | 1,859 MW | 2,977 MW | 0 MW | 1,520 MW | 340 MW |
| 06:00 | 2,050 MW | 3,175 MW | 12 MW | 1,582 MW | 456 MW |
| 07:00 | 2,240 MW | 3,413 MW | 211 MW | 1,571 MW | 459 MW |
| 08:00 | 2,331 MW | 3,726 MW | 744 MW | 1,524 MW | 63 MW |
| 09:00 | 2,320 MW | 3,882 MW | 1,288 MW | 1,444 MW | -412 MW |
| 10:00 | 2,312 MW | 3,968 MW | 1,613 MW | 1,410 MW | -711 MW |
| 11:00 | 2,279 MW | 3,955 MW | 1,765 MW | 1,388 MW | -873 MW |
| 12:00 | 2,336 MW | 3,935 MW | 1,749 MW | 1,390 MW | -803 MW |
| 13:00 | 2,267 MW | 3,887 MW | 1,623 MW | 1,449 MW | -805 MW |
| 14:00 | 2,200 MW | 3,772 MW | 1,377 MW | 1,498 MW | -676 MW |
| 15:00 | 2,239 MW | 3,744 MW | 955 MW | 1,623 MW | -339 MW |
| 16:00 | 2,329 MW | 3,776 MW | 459 MW | 1,684 MW | 186 MW |
| 17:00 | 2,525 MW | 3,909 MW | 109 MW | 1,611 MW | 805 MW |
| 18:00 | 2,652 MW | 3,928 MW | 2 MW | 1,500 MW | 1,150 MW |
| 19:00 | 2,704 MW | 3,907 MW | 1 MW | 1,440 MW | 1,264 MW |
| 20:00 | 2,673 MW | 3,823 MW | 0 MW | 1,383 MW | 1,290 MW |
| 21:00 | 2,525 MW | 3,747 MW | 0 MW | 1,348 MW | 1,177 MW |
| 22:00 | 2,370 MW | 3,723 MW | 0 MW | 1,353 MW | 1,018 MW |
| 23:00 | 2,210 MW | 3,606 MW | 0 MW | 1,352 MW | 857 MW |
Each value is the mean over 28 complete local days from 8 October to 4 November 2026, weekdays and weekends together, for the hour starting at that local clock time. Net load is demand minus solar and wind generation. The single highest hour of demand in the whole 30 day window was 3,186 MW; it is a published reading, not an average, and is not part of the profile above.
Source: ENTSO-E Transparency Platform (transparency.entsoe.eu), CC BY 4.0. Aggregated and converted by World Power Monitor; ENTSO-E does not endorse this site. (ENTSO-E Terms of Use plus CC BY 4.0 for listed data items) Data as of 2026-11-04. Profiles are computed by World Power Monitor from the operator's hourly series.
Assumptions
- Hours are local clock time in Europe/Rome. A local day is used only if it is whole inside the 30 day window and at least 22 of its hours are complete; the profile uses the 28 most recent such days. Daylight saving follows the local clock: on a clock change day the missing hour is absent and the repeated hour is averaged over both readings.
- The average mixes weekdays and weekends and covers only 28 days, so it describes recent conditions, not a seasonal norm.
- The evening ramp is the largest rise over three hours in the average profile, starting between 14:00 and 20:00 local time.
Related
Cite this page
World Power Monitor. (2026). Italy South Daily Load Shape and Duck Curve by Hour. https://worldpowermonitor.com/load-shapes/it-sud/
World Power Monitor. Italy South Daily Load Shape and Duck Curve by Hour. Data as of 2026-11-04. Data from ENTSO-E Transparency Platform. https://worldpowermonitor.com/load-shapes/it-sud/
@misc{wpm_load_shapes_it_sud_2026,
title = {{Italy South Daily Load Shape and Duck Curve by Hour}},
author = {{World Power Monitor}},
year = {2026},
note = {Data as of 2026-11-04. Data from ENTSO-E Transparency Platform.},
url = {https://worldpowermonitor.com/load-shapes/it-sud/}
} Permalink: https://worldpowermonitor.com/load-shapes/it-sud/
The Copy buttons add today's date as the access date.