TEC Daily Load Shape and Duck Curve by Hour, 7 October to 4 November 2026

In the 29 complete local days from 7 October to 4 November 2026, electricity demand in TEC averaged 2,441 MW and typically peaked at 17:00 local time (3,077 MW) and bottomed out at 03:00 (1,807 MW). With solar taken off, the remaining load fell to 1,651 MW at 09:00 and then rose 625 MW between 15:00 to 18:00. Hours are local clock time (America/New_York).

Key Facts

  • Over 29 complete local days from 7 October to 4 November 2026, average demand in TEC was 2,441 MW. The hour of the day with the highest average demand was 17:00 local time (3,077 MW) and the lowest was 03:00 (1,807 MW).
  • The largest three hour rise in average demand was 164 MW, between 14:00 to 17:00 local time.
  • The single highest hour of demand in the 30 day window was 3,875 MW, in the hour starting 15 Oct 2026, 17:00 EDT (UTC-04:00).
  • Solar output averaged 752 MW at its 13:00 peak, 31% of average demand.
  • Demand minus solar (net load) averaged 2,175 MW, fell to 1,651 MW at 09:00 and rose 625 MW over the three hours from 15:00 to 18:00, 26% of average demand.

Average Day by Local Hour

29 days to 2026-11-04, America/New_York time
TEC average demand and net generation by local hour Average electricity demand in TEC by local clock hour over 29 complete local days from 7 October to 4 November 2026. It was lowest at 03:00 (1,807 MW) and highest at 17:00 (3,077 MW). Net generation is the power produced inside the grid, so it differs from demand by net imports. 0 1,000 2,000 3,000 4,000 00:0003:0006:0009:0012:0015:0018:0021:00
Average electricity demand in TEC by local clock hour over 29 complete local days from 7 October to 4 November 2026. It was lowest at 03:00 (1,807 MW) and highest at 17:00 (3,077 MW). Net generation is the power produced inside the grid, so it differs from demand by net imports.
Mean MW by local hour, 2026-10-07 to 2026-11-04
TEC average demand and net generation by local hour
Local hour (America/New_York)DemandNet generation
00:002,082 MW2,094 MW
01:001,948 MW1,961 MW
02:001,856 MW1,869 MW
03:001,807 MW1,819 MW
04:001,808 MW1,827 MW
05:001,880 MW1,907 MW
06:002,005 MW2,030 MW
07:002,077 MW2,107 MW
08:002,157 MW2,195 MW
09:002,297 MW2,355 MW
10:002,425 MW2,476 MW
11:002,545 MW2,587 MW
12:002,679 MW2,706 MW
13:002,806 MW2,819 MW
14:002,913 MW2,859 MW
15:003,007 MW2,797 MW
16:003,070 MW2,810 MW
17:003,077 MW2,775 MW
18:003,009 MW2,691 MW
19:002,951 MW2,635 MW
20:002,818 MW2,522 MW
21:002,657 MW2,458 MW
22:002,458 MW2,411 MW
23:002,253 MW2,238 MW
TEC duck curve: demand and net load by local hour Average demand and net load (demand minus solar) in TEC by local clock hour over 29 complete local days from 7 October to 4 November 2026. Net load was lowest at 09:00 (1,651 MW) and then rose 625 MW between 15:00 to 18:00. 0 1,000 2,000 3,000 4,000 00:0003:0006:0009:0012:0015:0018:0021:00
Average demand and net load (demand minus solar) in TEC by local clock hour over 29 complete local days from 7 October to 4 November 2026. Net load was lowest at 09:00 (1,651 MW) and then rose 625 MW between 15:00 to 18:00.
Mean MW by local hour, 2026-10-07 to 2026-11-04
TEC duck curve: demand and net load by local hour
Local hour (America/New_York)DemandNet load (demand minus solar)
00:002,082 MW2,082 MW
01:001,948 MW1,948 MW
02:001,856 MW1,856 MW
03:001,807 MW1,807 MW
04:001,808 MW1,808 MW
05:001,880 MW1,880 MW
06:002,005 MW2,004 MW
07:002,077 MW2,056 MW
08:002,157 MW1,850 MW
09:002,297 MW1,651 MW
10:002,425 MW1,710 MW
11:002,545 MW1,809 MW
12:002,679 MW1,932 MW
13:002,806 MW2,054 MW
14:002,913 MW2,164 MW
15:003,007 MW2,314 MW
16:003,070 MW2,502 MW
17:003,077 MW2,727 MW
18:003,009 MW2,940 MW
19:002,951 MW2,931 MW
20:002,818 MW2,813 MW
21:002,657 MW2,653 MW
22:002,458 MW2,453 MW
23:002,253 MW2,252 MW
TEC average solar output by local hour Average solar generation in TEC by local clock hour over 29 complete local days from 7 October to 4 November 2026. Solar peaked at 13:00 at 752 MW. 0 200 400 600 800 00:0003:0006:0009:0012:0015:0018:0021:00
Average solar generation in TEC by local clock hour over 29 complete local days from 7 October to 4 November 2026. Solar peaked at 13:00 at 752 MW.
Mean MW by local hour, 2026-10-07 to 2026-11-04
TEC average solar output by local hour
Local hour (America/New_York)Solar
00:000 MW
01:000 MW
02:000 MW
03:000 MW
04:000 MW
05:000 MW
06:001 MW
07:0020 MW
08:00307 MW
09:00646 MW
10:00715 MW
11:00736 MW
12:00747 MW
13:00752 MW
14:00749 MW
15:00692 MW
16:00568 MW
17:00350 MW
18:0069 MW
19:0020 MW
20:005 MW
21:004 MW
22:005 MW
23:001 MW
Average TEC demand, net generation, solar and net load by local hour
Local hourDemandNet generationSolarNet load
00:00 2,082 MW 2,094 MW 0 MW 2,082 MW
01:00 1,948 MW 1,961 MW 0 MW 1,948 MW
02:00 1,856 MW 1,869 MW 0 MW 1,856 MW
03:00 1,807 MW 1,819 MW 0 MW 1,807 MW
04:00 1,808 MW 1,827 MW 0 MW 1,808 MW
05:00 1,880 MW 1,907 MW 0 MW 1,880 MW
06:00 2,005 MW 2,030 MW 1 MW 2,004 MW
07:00 2,077 MW 2,107 MW 20 MW 2,056 MW
08:00 2,157 MW 2,195 MW 307 MW 1,850 MW
09:00 2,297 MW 2,355 MW 646 MW 1,651 MW
10:00 2,425 MW 2,476 MW 715 MW 1,710 MW
11:00 2,545 MW 2,587 MW 736 MW 1,809 MW
12:00 2,679 MW 2,706 MW 747 MW 1,932 MW
13:00 2,806 MW 2,819 MW 752 MW 2,054 MW
14:00 2,913 MW 2,859 MW 749 MW 2,164 MW
15:00 3,007 MW 2,797 MW 692 MW 2,314 MW
16:00 3,070 MW 2,810 MW 568 MW 2,502 MW
17:00 3,077 MW 2,775 MW 350 MW 2,727 MW
18:00 3,009 MW 2,691 MW 69 MW 2,940 MW
19:00 2,951 MW 2,635 MW 20 MW 2,931 MW
20:00 2,818 MW 2,522 MW 5 MW 2,813 MW
21:00 2,657 MW 2,458 MW 4 MW 2,653 MW
22:00 2,458 MW 2,411 MW 5 MW 2,453 MW
23:00 2,253 MW 2,238 MW 1 MW 2,252 MW

Each value is the mean over 29 complete local days from 7 October to 4 November 2026, weekdays and weekends together, for the hour starting at that local clock time. Net load is demand minus solar generation. The single highest hour of demand in the whole 30 day window was 3,875 MW; it is a published reading, not an average, and is not part of the profile above.

Source: U.S. Energy Information Administration (EIA). (US Government work, public domain) Data as of 2026-11-04. Profiles are computed by World Power Monitor from the operator's hourly series.

Assumptions

  • Hours are local clock time in America/New_York. A local day is used only if it is whole inside the 30 day window and at least 22 of its hours are complete; the profile uses the 29 most recent such days. Daylight saving follows the local clock: on a clock change day the missing hour is absent and the repeated hour is averaged over both readings.
  • The average mixes weekdays and weekends and covers only 29 days, so it describes recent conditions, not a seasonal norm.
  • The evening ramp is the largest rise over three hours in the average profile, starting between 14:00 and 20:00 local time.
Cite this page
APA 7

World Power Monitor. (2026). TEC Daily Load Shape and Duck Curve by Hour. https://worldpowermonitor.com/load-shapes/tec/

Plain text

World Power Monitor. TEC Daily Load Shape and Duck Curve by Hour. Data as of 2026-11-04. Data from U.S. Energy Information Administration. https://worldpowermonitor.com/load-shapes/tec/

BibTeX
@misc{wpm_load_shapes_tec_2026,
  title = {{TEC Daily Load Shape and Duck Curve by Hour}},
  author = {{World Power Monitor}},
  year = {2026},
  note = {Data as of 2026-11-04. Data from U.S. Energy Information Administration.},
  url = {https://worldpowermonitor.com/load-shapes/tec/}
}

Permalink: https://worldpowermonitor.com/load-shapes/tec/