Denmark West (DK1) Daily Load Shape and Duck Curve by Hour, 8 to 29 October 2026
In the 18 complete local days from 8 to 29 October 2026, electricity demand in Denmark West (DK1) averaged 2,837 MW and typically peaked at 13:00 local time (3,358 MW) and bottomed out at 05:00 (2,409 MW). With solar and wind taken off, the remaining load fell to 38 MW at 12:00 and then rose 598 MW between 14:00 to 17:00. Hours are local clock time (Europe/Copenhagen).
Key Facts
- Over 18 complete local days from 8 to 29 October 2026, average demand in Denmark West (DK1) was 2,837 MW. The hour of the day with the highest average demand was 13:00 local time (3,358 MW) and the lowest was 05:00 (2,409 MW).
- The single highest hour of demand in the 30 day window was 3,872 MW, in the hour starting 26 Oct 2026, 11:00 CET (UTC+01:00).
- Solar output averaged 1,174 MW at its 12:00 peak, 41% of average demand.
- Demand minus solar and wind (net load) averaged 568 MW, fell to 38 MW at 12:00 and rose 598 MW over the three hours from 14:00 to 17:00, 21% of average demand.
Average Day by Local Hour
18 days to 2026-10-29, Europe/Copenhagen time| Local hour (Europe/Copenhagen) | Demand | Net generation |
|---|---|---|
| 00:00 | 2,611 MW | 3,041 MW |
| 01:00 | 2,614 MW | 2,839 MW |
| 02:00 | 2,620 MW | 2,771 MW |
| 03:00 | 2,575 MW | 2,748 MW |
| 04:00 | 2,473 MW | 2,725 MW |
| 05:00 | 2,409 MW | 2,740 MW |
| 06:00 | 2,555 MW | 2,866 MW |
| 07:00 | 2,796 MW | 2,959 MW |
| 08:00 | 2,904 MW | 3,008 MW |
| 09:00 | 3,011 MW | 3,449 MW |
| 10:00 | 3,138 MW | 3,815 MW |
| 11:00 | 3,218 MW | 4,098 MW |
| 12:00 | 3,269 MW | 4,168 MW |
| 13:00 | 3,358 MW | 4,142 MW |
| 14:00 | 3,267 MW | 3,999 MW |
| 15:00 | 3,111 MW | 3,808 MW |
| 16:00 | 3,015 MW | 3,585 MW |
| 17:00 | 3,037 MW | 3,389 MW |
| 18:00 | 2,961 MW | 3,344 MW |
| 19:00 | 2,804 MW | 3,365 MW |
| 20:00 | 2,700 MW | 3,322 MW |
| 21:00 | 2,635 MW | 3,265 MW |
| 22:00 | 2,529 MW | 3,218 MW |
| 23:00 | 2,486 MW | 3,162 MW |
| Local hour (Europe/Copenhagen) | Demand | Net load (demand minus solar and wind) |
|---|---|---|
| 00:00 | 2,611 MW | 654 MW |
| 01:00 | 2,614 MW | 799 MW |
| 02:00 | 2,620 MW | 832 MW |
| 03:00 | 2,575 MW | 793 MW |
| 04:00 | 2,473 MW | 712 MW |
| 05:00 | 2,409 MW | 624 MW |
| 06:00 | 2,555 MW | 699 MW |
| 07:00 | 2,796 MW | 912 MW |
| 08:00 | 2,904 MW | 1,012 MW |
| 09:00 | 3,011 MW | 698 MW |
| 10:00 | 3,138 MW | 394 MW |
| 11:00 | 3,218 MW | 115 MW |
| 12:00 | 3,269 MW | 38 MW |
| 13:00 | 3,358 MW | 149 MW |
| 14:00 | 3,267 MW | 216 MW |
| 15:00 | 3,111 MW | 278 MW |
| 16:00 | 3,015 MW | 482 MW |
| 17:00 | 3,037 MW | 814 MW |
| 18:00 | 2,961 MW | 836 MW |
| 19:00 | 2,804 MW | 664 MW |
| 20:00 | 2,700 MW | 567 MW |
| 21:00 | 2,635 MW | 524 MW |
| 22:00 | 2,529 MW | 427 MW |
| 23:00 | 2,486 MW | 394 MW |
| Local hour (Europe/Copenhagen) | Solar | Wind |
|---|---|---|
| 00:00 | 49 MW | 1,908 MW |
| 01:00 | 48 MW | 1,767 MW |
| 02:00 | 48 MW | 1,741 MW |
| 03:00 | 48 MW | 1,734 MW |
| 04:00 | 48 MW | 1,713 MW |
| 05:00 | 48 MW | 1,738 MW |
| 06:00 | 49 MW | 1,807 MW |
| 07:00 | 68 MW | 1,816 MW |
| 08:00 | 178 MW | 1,714 MW |
| 09:00 | 512 MW | 1,801 MW |
| 10:00 | 930 MW | 1,813 MW |
| 11:00 | 1,172 MW | 1,930 MW |
| 12:00 | 1,174 MW | 2,057 MW |
| 13:00 | 1,129 MW | 2,079 MW |
| 14:00 | 974 MW | 2,077 MW |
| 15:00 | 774 MW | 2,060 MW |
| 16:00 | 502 MW | 2,031 MW |
| 17:00 | 204 MW | 2,019 MW |
| 18:00 | 98 MW | 2,027 MW |
| 19:00 | 96 MW | 2,044 MW |
| 20:00 | 69 MW | 2,064 MW |
| 21:00 | 54 MW | 2,057 MW |
| 22:00 | 53 MW | 2,049 MW |
| 23:00 | 47 MW | 2,045 MW |
| Local hour | Demand | Net generation | Solar | Wind | Net load |
|---|---|---|---|---|---|
| 00:00 | 2,611 MW | 3,041 MW | 49 MW | 1,908 MW | 654 MW |
| 01:00 | 2,614 MW | 2,839 MW | 48 MW | 1,767 MW | 799 MW |
| 02:00 | 2,620 MW | 2,771 MW | 48 MW | 1,741 MW | 832 MW |
| 03:00 | 2,575 MW | 2,748 MW | 48 MW | 1,734 MW | 793 MW |
| 04:00 | 2,473 MW | 2,725 MW | 48 MW | 1,713 MW | 712 MW |
| 05:00 | 2,409 MW | 2,740 MW | 48 MW | 1,738 MW | 624 MW |
| 06:00 | 2,555 MW | 2,866 MW | 49 MW | 1,807 MW | 699 MW |
| 07:00 | 2,796 MW | 2,959 MW | 68 MW | 1,816 MW | 912 MW |
| 08:00 | 2,904 MW | 3,008 MW | 178 MW | 1,714 MW | 1,012 MW |
| 09:00 | 3,011 MW | 3,449 MW | 512 MW | 1,801 MW | 698 MW |
| 10:00 | 3,138 MW | 3,815 MW | 930 MW | 1,813 MW | 394 MW |
| 11:00 | 3,218 MW | 4,098 MW | 1,172 MW | 1,930 MW | 115 MW |
| 12:00 | 3,269 MW | 4,168 MW | 1,174 MW | 2,057 MW | 38 MW |
| 13:00 | 3,358 MW | 4,142 MW | 1,129 MW | 2,079 MW | 149 MW |
| 14:00 | 3,267 MW | 3,999 MW | 974 MW | 2,077 MW | 216 MW |
| 15:00 | 3,111 MW | 3,808 MW | 774 MW | 2,060 MW | 278 MW |
| 16:00 | 3,015 MW | 3,585 MW | 502 MW | 2,031 MW | 482 MW |
| 17:00 | 3,037 MW | 3,389 MW | 204 MW | 2,019 MW | 814 MW |
| 18:00 | 2,961 MW | 3,344 MW | 98 MW | 2,027 MW | 836 MW |
| 19:00 | 2,804 MW | 3,365 MW | 96 MW | 2,044 MW | 664 MW |
| 20:00 | 2,700 MW | 3,322 MW | 69 MW | 2,064 MW | 567 MW |
| 21:00 | 2,635 MW | 3,265 MW | 54 MW | 2,057 MW | 524 MW |
| 22:00 | 2,529 MW | 3,218 MW | 53 MW | 2,049 MW | 427 MW |
| 23:00 | 2,486 MW | 3,162 MW | 47 MW | 2,045 MW | 394 MW |
Each value is the mean over 18 complete local days from 8 to 29 October 2026, weekdays and weekends together, for the hour starting at that local clock time. Net load is demand minus solar and wind generation. The single highest hour of demand in the whole 30 day window was 3,872 MW; it is a published reading, not an average, and is not part of the profile above.
Source: ENTSO-E Transparency Platform (transparency.entsoe.eu), CC BY 4.0. Aggregated and converted by World Power Monitor; ENTSO-E does not endorse this site. (ENTSO-E Terms of Use plus CC BY 4.0 for listed data items) Data as of 2026-10-29. Profiles are computed by World Power Monitor from the operator's hourly series.
Assumptions
- Hours are local clock time in Europe/Copenhagen. A local day is used only if it is whole inside the 30 day window and at least 22 of its hours are complete; the profile uses the 18 most recent such days. Daylight saving follows the local clock: on a clock change day the missing hour is absent and the repeated hour is averaged over both readings.
- The average mixes weekdays and weekends and covers only 18 days, so it describes recent conditions, not a seasonal norm.
- The evening ramp is the largest rise over three hours in the average profile, starting between 14:00 and 20:00 local time.
Related
Cite this page
World Power Monitor. (2026). Denmark West (DK1) Daily Load Shape and Duck Curve by Hour. https://worldpowermonitor.com/load-shapes/dk1/
World Power Monitor. Denmark West (DK1) Daily Load Shape and Duck Curve by Hour. Data as of 2026-10-29. Data from ENTSO-E Transparency Platform. https://worldpowermonitor.com/load-shapes/dk1/
@misc{wpm_load_shapes_dk1_2026,
title = {{Denmark West (DK1) Daily Load Shape and Duck Curve by Hour}},
author = {{World Power Monitor}},
year = {2026},
note = {Data as of 2026-10-29. Data from ENTSO-E Transparency Platform.},
url = {https://worldpowermonitor.com/load-shapes/dk1/}
} Permalink: https://worldpowermonitor.com/load-shapes/dk1/
The Copy buttons add today's date as the access date.